#1
![]() |
|||
|
|||
![]()
I don't know if this qualifies as cheap enough but one way is to use a
variable autotransformer, a transformer with a variable tap. With 120VAC in you can output from 0130 VAC. Here is a link to a 10amp unit all cased up and ready to plug in. If you are handy you can get the transformer itself for a lot less. http://www.tenma.com/070.html BTW, 9 amps seems kinda high, I would expect a 40amp charger to draw about half that on the line side. The other thing to keep in mind is that these use a wiper to vary the tap, I have no idea how long that would last on a boat. RB .. Panama wrote: I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) |
#2
![]() |
|||
|
|||
![]()
Panama wrote:
.....Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) Is it less expensive to continually buy new batteries after your old cheap battery charger fries them? Priorities, man! DSK |
#3
![]() |
|||
|
|||
![]()
Panama wrote:
.....Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) Is it less expensive to continually buy new batteries after your old cheap battery charger fries them? Priorities, man! DSK |
#4
![]() |
|||
|
|||
![]()
Throw out that charger and get a good one. Those kinds of
variations in line voltage should not affect the output. I've seen line voltages from 105 to 128 in our travels and the battery charger always maintains the proper voltages and currents. By the time you get a way to control the line voltage you can by a new charger that works properly. Doug s/v Callista "Panama" wrote in message ... I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) |
#5
![]() |
|||
|
|||
![]()
Throw out that charger and get a good one. Those kinds of
variations in line voltage should not affect the output. I've seen line voltages from 105 to 128 in our travels and the battery charger always maintains the proper voltages and currents. By the time you get a way to control the line voltage you can by a new charger that works properly. Doug s/v Callista "Panama" wrote in message ... I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) |
#6
![]() |
|||
|
|||
![]()
Sounds like you need an "autotransformer".
Many Variacs are actually autotransformers, in that they accept 110V input, and output from 0 to 130 volts AC. The principle works as such: ======================= mmmmmmmmmmmmmmmm | | ^ A B C If you supply the inputs to wires A and B, and outputs on A and C, and C is the adjustable portion of the Vairac. If the voltage from A - B is 110 Volts, when C is farther out on the transformer, you will see a higher voltage from A - C (above 110 Volts). When it is inside of B you will reduce the voltage (below 110 Volts). My bench Variac actually inputs 110V, and outputs from 0 to 220V. You can also do this with a multi-voltage transformer: Do not care about Secondary ========================== mmmmmmmmmmmmmmmmmm | | | | | A B C D E 100 110 120 130 This is a common multi-input voltage transformer used in international equipment, having inputs of 100, 110, 120, 130 Volts. This will typically be a low voltage transformer, but you really don't care about the secondary side. If you typically see from 100 to 130 volts and you want 110 volts, you would hook up the output to A-C. and the input to: 100V A - B 110V A - C 120V A - D 130V A - E With this setup, you will boost or decrease the voltage depending on where you have the input. You will need to find a transformer large enough to supply your peak wattage, and remember that even if you normally draw 9A at 110V, in the 100 V boost configuration, your input current will be 9.9A. Also autotransformers DO NOT isolate the secondary from the line, so electrical shock is still possible. "Panama" wrote in message ... I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) |
#7
![]() |
|||
|
|||
![]()
On Sun, 23 Nov 2003 16:43:03 -0800, Panama wrote:
I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) Seems like I answered this in another newsgroup, but if you missed it... There are two types of auto-regulating transformers. The old kind uses a swinging core. As the voltage varies, the core moves in and out to provide a more or less constant voltage. I say "more or less" as they can seldom act fast enough to block transients, those very short term spikes which can damage electronic gear. The second type are called "ferro-resonant" transformers. They work by driving the core into saturation and operate in parallel with a non-polarized capacitor to ensure that the output voltage always remains the same. They offer a few advantages, the best being that they do not transfer voltage transients (spikes). Both are rated in volt-amps and both are available on the surplus market. Good luck -- Larry email is rapp at lmr dot com |
#8
![]() |
|||
|
|||
![]()
Sounds like you need an "autotransformer".
Many Variacs are actually autotransformers, in that they accept 110V input, and output from 0 to 130 volts AC. The principle works as such: ======================= mmmmmmmmmmmmmmmm | | ^ A B C If you supply the inputs to wires A and B, and outputs on A and C, and C is the adjustable portion of the Vairac. If the voltage from A - B is 110 Volts, when C is farther out on the transformer, you will see a higher voltage from A - C (above 110 Volts). When it is inside of B you will reduce the voltage (below 110 Volts). My bench Variac actually inputs 110V, and outputs from 0 to 220V. You can also do this with a multi-voltage transformer: Do not care about Secondary ========================== mmmmmmmmmmmmmmmmmm | | | | | A B C D E 100 110 120 130 This is a common multi-input voltage transformer used in international equipment, having inputs of 100, 110, 120, 130 Volts. This will typically be a low voltage transformer, but you really don't care about the secondary side. If you typically see from 100 to 130 volts and you want 110 volts, you would hook up the output to A-C. and the input to: 100V A - B 110V A - C 120V A - D 130V A - E With this setup, you will boost or decrease the voltage depending on where you have the input. You will need to find a transformer large enough to supply your peak wattage, and remember that even if you normally draw 9A at 110V, in the 100 V boost configuration, your input current will be 9.9A. Also autotransformers DO NOT isolate the secondary from the line, so electrical shock is still possible. "Panama" wrote in message ... I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) |
#9
![]() |
|||
|
|||
![]()
On Sun, 23 Nov 2003 16:43:03 -0800, Panama wrote:
I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) Seems like I answered this in another newsgroup, but if you missed it... There are two types of auto-regulating transformers. The old kind uses a swinging core. As the voltage varies, the core moves in and out to provide a more or less constant voltage. I say "more or less" as they can seldom act fast enough to block transients, those very short term spikes which can damage electronic gear. The second type are called "ferro-resonant" transformers. They work by driving the core into saturation and operate in parallel with a non-polarized capacitor to ensure that the output voltage always remains the same. They offer a few advantages, the best being that they do not transfer voltage transients (spikes). Both are rated in volt-amps and both are available on the surplus market. Good luck -- Larry email is rapp at lmr dot com |
#10
![]() |
|||
|
|||
![]()
Panama wrote:
I have a 40 amp battery charger that has a 5 position switch to select the battery charging voltage. Works great. Allows steps from about 13.2 to 17 volts. Prob done by a multi-tap transformer? Trouble is - AC voltages in Mexico can be as high as 128-130 VAC and other places can be as low as 105 VAC. The charger reacts by changing the battery charging voltage up or down - a little but enough to vary the DC amps that get to the batteries. I'm not going to replace the charger. I'm looking for a cheap variac/scr/triac something gizmo that I can wire into the AC line to the charger and make the effective voltage (RMS value?) go up or down by +/- 10% or so. The AC in is about max 9 amps. It could even be a big wired wound variable resistor I suppose. Then I can set the AC line voltage to what my genset puts out and use the charger at it's max 40 amps all the time. Any ideas or products. Preferably cheap and never needs replacement like the 27 years old charger. (No I'm really not going to replace the charger.) The specified/allowed 'Voltage variation' plus/minus varies (pun intended!) a little from country to country and region to region. E.g. North America, Europe, etc. In some places it may be plus and minus ten (10) per cent. In another area it may be, say, minus 6% to plus 10%. If in Mexico the voltage is occasionally up to 128/130 on a supply that is supposed to be 117/120 volts; that's around 9% to 11% high. i.e. acceptable? If you are monitoring it anyway why worry? Is in danger of burning out. i so tap it down to the next lower ampere/voltage output setting? Or am I missing something? |