On Sat, 26 Jan 2008 10:19:06 -0500, "Eisboch" wrote:

If the generator shuts down ok by *removing* the 10 amp fuse that normally
blows if using one of the kill switches, it suggests that a solenoid or
something is *energized* while running. The kill switches must interrupt
the power to something .... same as removing the fuse.


I have an Onan diesel generator that works pretty much as you
describe. There is a solenoid which must be activated for the
generator to start and continue running. If an over temp or low oil
pressure sensor trips, power to the solenoid is interuppted and the
generator stops. It will not restart until a reset button is pressed.
When you press the stop button, a relay is activated which interrupts
power to the solenoid. My guess would be a short circuit or defective
shut down relay.
  #12   Report Post  
posted to rec.outdoors.rv-travel,alt.rv,rec.boats,rec.boats.building
external usenet poster
 
First recorded activity by BoatBanter: May 2007
Posts: 2,587
Default Kohler 6.5KW CZ generator blowing fuse

On Sun, 27 Jan 2008 09:51:00 -0500, Wayne.B
wrote:

If the generator shuts down ok by *removing* the 10 amp fuse that normally
blows


My Maytag washer and drier have the wiring diagrams pasted to the
inside of the removable sheet metal access panels. Maytag is no more,
unfortunately.

Casady
  #13   Report Post  
posted to rec.outdoors.rv-travel,alt.rv,rec.boats,rec.boats.building
external usenet poster
 
First recorded activity by BoatBanter: Jul 2006
Posts: 8,995
Default Kohler 6.5KW CZ generator blowing fuse


"Richard Casady" wrote in message
.. .
On Sun, 27 Jan 2008 09:51:00 -0500, Wayne.B
wrote:

If the generator shuts down ok by *removing* the 10 amp fuse that
normally
blows


My Maytag washer and drier have the wiring diagrams pasted to the
inside of the removable sheet metal access panels. Maytag is no more,
unfortunately.

Casady



Whirlpool still use the Mmaytag name but the appliances aren't what they
used to be... re massive recall last year.


  #14   Report Post  
posted to rec.outdoors.rv-travel,alt.rv,rec.boats,rec.boats.building
external usenet poster
 
First recorded activity by BoatBanter: Jan 2008
Posts: 2
Default Kohler 6.5KW CZ generator blowing fuse

On Sun, 27 Jan 2008 13:04:39 -0400, "Don White"
wrote:


"Richard Casady" wrote in message
. ..
On Sun, 27 Jan 2008 09:51:00 -0500, Wayne.B
wrote:

If the generator shuts down ok by *removing* the 10 amp fuse that
normally
blows


My Maytag washer and drier have the wiring diagrams pasted to the
inside of the removable sheet metal access panels. Maytag is no more,
unfortunately.

Casady



Whirlpool still use the Mmaytag name but the appliances aren't what they
used to be... re massive recall last year.

Maytag is still very much in business. Check http://www.maytag.com
In addition they own many other brands such as Whirlpool, Amana, etc.

George

--
Posted via a free Usenet account from http://www.teranews.com

  #15   Report Post  
posted to rec.outdoors.rv-travel,alt.rv,rec.boats,rec.boats.building
external usenet poster
 
First recorded activity by BoatBanter: Jul 2006
Posts: 8,995
Default Kohler 6.5KW CZ generator blowing fuse


wrote in message
...
On Sun, 27 Jan 2008 13:04:39 -0400, "Don White"
wrote:


"Richard Casady" wrote in message
...
On Sun, 27 Jan 2008 09:51:00 -0500, Wayne.B
wrote:

If the generator shuts down ok by *removing* the 10 amp fuse that
normally
blows

My Maytag washer and drier have the wiring diagrams pasted to the
inside of the removable sheet metal access panels. Maytag is no more,
unfortunately.

Casady



Whirlpool still use the Mmaytag name but the appliances aren't what they
used to be... re massive recall last year.

Maytag is still very much in business. Check http://www.maytag.com
In addition they own many other brands such as Whirlpool, Amana, etc.

George

--

eerrr...i think you have that backwards...Whirlpool bought Maytag.
I know this because I was one of those affected by the inner door/control
panel fiasco last year. Finally got a new dishwasher out of it.




  #16   Report Post  
posted to rec.outdoors.rv-travel, alt.rv, rec.boats, rec.boats.building
GSS GSS is offline
external usenet poster
 
First recorded activity by BoatBanter: Aug 2006
Posts: 19
Default Kohler 6.5KW CZ generator blowing fuse

On Jan 27, 1:50*pm, "Don White" wrote:
wrote in message

...



On Sun, 27 Jan 2008 13:04:39 -0400, "Don White"
wrote:


"Richard Casady" wrote in message
...
On Sun, 27 Jan 2008 09:51:00 -0500, Wayne.B
wrote:


If the generator shuts down ok by *removing* the 10 amp fuse that
normally
blows


My Maytag washer and drier have the wiring diagrams pasted to the
inside of the removable sheet metal access panels. Maytag is no more,
unfortunately.


Casady


Whirlpool still use the Mmaytag name but the appliances aren't what they
used to be... re massive recall last year.


Maytag is still very much in business. *Check http://www.maytag.com
In addition they own many other brands such as Whirlpool, Amana, etc.


George


--


eerrr...i think you have that backwards...Whirlpool bought Maytag.
I know this because I was one of those affected by the inner door/control
panel fiasco last year. * Finally got a new dishwasher out of it.- Hide quoted text -

- Show quoted text -


The input fuse is the fuse which protects the whole control
panel...I've determined that from the schematic which was as a
previous poster suggested. The stop sequence activates a number of
relays any one of which could be shorting & blowing the fuse. The
engine is killed from a "fuel solenoid", which I believe connects to
the Carbeuretor and may choke the engine. I found a kohler parts
schematic and it looks like I'll need to replace the whole panel...the
relays are not removable. Thanks for all the help!
  #17   Report Post  
posted to rec.outdoors.rv-travel,alt.rv,rec.boats,rec.boats.building
external usenet poster
 
First recorded activity by BoatBanter: Jan 2008
Posts: 2
Default Kohler 6.5KW CZ generator blowing fuse

GSS wrote:
I have a gas powered 6.5 KW Kohler generator Model 6.5CZ that blows
the 10 amp input fuse whenever I shut it down from the engine mounted
or remote kill switches.


This may not be related. However, I have a 20kw Kohler that kept blowing
fuses for no reason. I found out the improper fuse was installed. A 10
amp high heat ceramic fuse should have been used. The heat given off
from the generator engine would heat up the fuse, and de-rate it. A
ceramic fuse is designed to operate in high ambient temperatures.

I hope this helps.
John
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is Off
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
240 v fuse-12v fuse switch problem MEC Electronics 4 December 22nd 06 10:21 AM
kohler generator carbon fouling kohler gen Cruising 3 September 16th 06 06:47 PM
blowing 15 amp main fuse!! brownie General 0 August 8th 06 04:09 PM
Kohler Generator Problem [email protected] Cruising 11 June 28th 06 12:54 AM
Kohler Generator Stopped Running snor General 7 August 25th 05 01:50 PM


All times are GMT +1. The time now is 07:15 PM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
Copyright ©2004-2025 BoatBanter.com.
The comments are property of their posters.
 

About Us

"It's about Boats"

 

Copyright © 2017