There is a second fuse, but this goes to the battery charging system
and seems to be unaffected by the stopping sequence. � Thanks in advance. Fuses have other characteristics than Amps. What type does the owners manual recommend? |
#2
![]()
posted to rec.outdoors.rv-travel,alt.rv,rec.boats,rec.boats.building
|
|||
|
|||
![]()
GSS wrote:
I have a gas powered 6.5 KW Kohler generator Model 6.5CZ that blows the 10 amp input fuse whenever I shut it down from the engine mounted or remote kill switches. This may not be related. However, I have a 20kw Kohler that kept blowing fuses for no reason. I found out the improper fuse was installed. A 10 amp high heat ceramic fuse should have been used. The heat given off from the generator engine would heat up the fuse, and de-rate it. A ceramic fuse is designed to operate in high ambient temperatures. I hope this helps. John |