Default Electrical Advice...

I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.



--
I'll believe corporations are people when Texas executes one.
  #2   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Sep 2011
Posts: 823
Default Electrical Advice...

On 10/4/2011 3:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.




You mean voltage drop, don't you? Here's a calculator
http://www.csgnetwork.com/voltagedropcalc.html

1. Probably.
2. Yup
3. Shop somewhere else or buy their minimum.

P.S. You need to satisfy local building codes irregardless of N E C. You
might even need permits and inspections.

You're a big boy. You should know how to interview and hire contractors.

  #3   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Oct 2009
Posts: 6,596
Default Electrical Advice...

On 04/10/2011 2:52 PM, Drifter wrote:
On 10/4/2011 3:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.




You mean voltage drop, don't you? Here's a calculator
http://www.csgnetwork.com/voltagedropcalc.html

1. Probably.
2. Yup
3. Shop somewhere else or buy their minimum.

P.S. You need to satisfy local building codes irregardless of N E C. You
might even need permits and inspections.

You're a big boy. You should know how to interview and hire contractors.



And a fuse box.


--
Eat the rich, screw the companies and wonder why there are no jobs.
-- Obama and the lefty fleabagger attitude
  #4   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Sep 2011
Posts: 823
Default Electrical Advice...

On 10/4/2011 10:45 PM, Canuck57 wrote:
On 04/10/2011 2:52 PM, Drifter wrote:
On 10/4/2011 3:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.




You mean voltage drop, don't you? Here's a calculator
http://www.csgnetwork.com/voltagedropcalc.html

1. Probably.
2. Yup
3. Shop somewhere else or buy their minimum.

P.S. You need to satisfy local building codes irregardless of N E C. You
might even need permits and inspections.

You're a big boy. You should know how to interview and hire contractors.



And a fuse box.


Do you think Krause meant to say 4GA instead of 4/0? I assumed he did.
There is a substantial size difference.
  #5   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Oct 2009
Posts: 6,596
Default Electrical Advice...

On 05/10/2011 5:57 AM, Drifter wrote:
On 10/4/2011 10:45 PM, Canuck57 wrote:
On 04/10/2011 2:52 PM, Drifter wrote:
On 10/4/2011 3:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a
17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and
above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.




You mean voltage drop, don't you? Here's a calculator
http://www.csgnetwork.com/voltagedropcalc.html

1. Probably.
2. Yup
3. Shop somewhere else or buy their minimum.

P.S. You need to satisfy local building codes irregardless of N E C. You
might even need permits and inspections.

You're a big boy. You should know how to interview and hire contractors.



And a fuse box.


Do you think Krause meant to say 4GA instead of 4/0? I assumed he did.
There is a substantial size difference.


Yep, he might have and a big difference too. In any case, it isn't a
end user task. He be best to get a qualified electrician that knows the
local codes.
--
Eat the rich, screw the companies and wonder why there are no jobs.
-- Obama and the lefty fleabagger attitude


  #6   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Aug 2011
Posts: 1,646
Default Electrical Advice...

On 10/5/11 5:01 PM, Canuck57 wrote:
On 05/10/2011 5:57 AM, Drifter wrote:
On 10/4/2011 10:45 PM, Canuck57 wrote:
On 04/10/2011 2:52 PM, Drifter wrote:
On 10/4/2011 3:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a
17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and
above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.




You mean voltage drop, don't you? Here's a calculator
http://www.csgnetwork.com/voltagedropcalc.html

1. Probably.
2. Yup
3. Shop somewhere else or buy their minimum.

P.S. You need to satisfy local building codes irregardless of N E C.
You
might even need permits and inspections.

You're a big boy. You should know how to interview and hire
contractors.


And a fuse box.


Do you think Krause meant to say 4GA instead of 4/0? I assumed he did.
There is a substantial size difference.


Yep, he might have and a big difference too. In any case, it isn't a end
user task. He be best to get a qualified electrician that knows the
local codes.



D'oh. I have no intention of installing a 17KW or 20KW generator at the
house. I've just been interviewing contractors and asking questions. The
install will be done by licensed electricians and a licensed plumber,
the latter one of the plumbers who works for our LP gas supplier. This
will be a replacement for a small capacity genny we've been using to
power a couple of circuits. The new one will run about half the house,
including one of our heat pumps, the well pump, a pair of refrigerators
and various lights and outlets.

--
I'll believe corporations are people when Texas executes one.
  #7   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Oct 2009
Posts: 6,596
Default Electrical Advice...

On 04/10/2011 1:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.


So is this for your grow op so the police don't see your utility bill?

In any case, for 1), current heats wire not voltage or wattage, so what
is the voltage as to calculate the current 17KW can generate? Amps
generate the heat. 220 or 115? With that size I will assume 220.
17K/220 = 77.3 amps. And I like being cautious, say AWG 3 for 220, 3/0
for 120.

http://en.wikipedia.org/wiki/American_wire_gauge

Probably industrial supply shops, as consumer hardware stores will not
carry this. As it gets worse. You need special tools to bend it, you
may need conduit and I strongly suspect local ordinance would require an
inspection or at least a licensed electrician.

--
Eat the rich, screw the companies and wonder why there are no jobs.
-- Obama and the lefty fleabagger attitude
  #8   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Jul 2009
Posts: 2,581
Default Electrical Advice...

On 10/4/2011 10:45 PM, Canuck57 wrote:
On 04/10/2011 1:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.


So is this for your grow op so the police don't see your utility bill?

In any case, for 1), current heats wire not voltage or wattage, so what
is the voltage as to calculate the current 17KW can generate? Amps
generate the heat. 220 or 115? With that size I will assume 220. 17K/220
= 77.3 amps. And I like being cautious, say AWG 3 for 220, 3/0 for 120.

http://en.wikipedia.org/wiki/American_wire_gauge

Probably industrial supply shops, as consumer hardware stores will not
carry this. As it gets worse. You need special tools to bend it, you may
need conduit and I strongly suspect local ordinance would require an
inspection or at least a licensed electrician.


Tonight I had to install a new shallow well system for a friend in
Essex. Pretty straight forward, pump, expansion tank, and new conduit
tube from the knife switch above on the floor joist, down to the cutoff
switch... to code.

We noticed the breaker supplied an outside light and an outlet too, so
we had to put in an new breaker and 12 ga, Romex to supply the pump on a
separate line, also required by code.

Electrical and plumbing is not really all that hard, about 20 years ago
I with some help changed my home over from knob and tube to modern day
romex, gpf switches, etc.., three years ago I redid the plumbing in
our place, including a new section of baseboard heating in one room. For
the water side of the system I used Pex pipe and Sharkbite fittings up
to the floors under the appliance or sink, and went with hard copper
from the floor up... I actually enjoy doing that stuff, But I guess my
bud could have waited for someone with "educational or professional
electrical background" and spent $700 for a $300 (parts) job we could
easily do ourselves. snerk.
  #9   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Aug 2011
Posts: 1,646
Default Electrical Advice...

On 10/5/11 1:05 AM, JustWait wrote:
On 10/4/2011 10:45 PM, Canuck57 wrote:
On 04/10/2011 1:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.


So is this for your grow op so the police don't see your utility bill?

In any case, for 1), current heats wire not voltage or wattage, so what
is the voltage as to calculate the current 17KW can generate? Amps
generate the heat. 220 or 115? With that size I will assume 220. 17K/220
= 77.3 amps. And I like being cautious, say AWG 3 for 220, 3/0 for 120.

http://en.wikipedia.org/wiki/American_wire_gauge

Probably industrial supply shops, as consumer hardware stores will not
carry this. As it gets worse. You need special tools to bend it, you may
need conduit and I strongly suspect local ordinance would require an
inspection or at least a licensed electrician.


Tonight I had to install a new shallow well system for a friend in
Essex. Pretty straight forward, pump, expansion tank, and new conduit
tube from the knife switch above on the floor joist, down to the cutoff
switch... to code.

We noticed the breaker supplied an outside light and an outlet too, so
we had to put in an new breaker and 12 ga, Romex to supply the pump on a
separate line, also required by code.

Electrical and plumbing is not really all that hard, about 20 years ago
I with some help changed my home over from knob and tube to modern day
romex, gpf switches, etc.., three years ago I redid the plumbing in
our place, including a new section of baseboard heating in one room. For
the water side of the system I used Pex pipe and Sharkbite fittings up
to the floors under the appliance or sink, and went with hard copper
from the floor up... I actually enjoy doing that stuff, But I guess my
bud could have waited for someone with "educational or professional
electrical background" and spent $700 for a $300 (parts) job we could
easily do ourselves. snerk.



I'll do light electrical work, such as replacing a wall switch or
ceiling fixture, but that's about it. The labor for the new generator
involves electricians and a plumber, and the charges for both services
are estimated at around $2500. The job has to be permitted, at least as
far as the plumbing goes. The genny is an LP gas appliance. I don't mess
with installing gas appliances or heavier duty electric, especially when
the wiring or pipes are to be concealed.



--
I'll believe corporations are people when Texas executes one.
  #10   Report Post  
posted to rec.boats
external usenet poster
 
First recorded activity by BoatBanter: Sep 2011
Posts: 7,588
Default Electrical Advice...

In article ,
says...

On 10/5/11 1:05 AM, JustWait wrote:
On 10/4/2011 10:45 PM, Canuck57 wrote:
On 04/10/2011 1:59 PM, X ` Man wrote:
I'm thinking of upgrading to a larger standby generator, probably a 17KW
model.

The generator will be approximately 50 to 60 feet away from the house
circuit breakers. The wire will run under the main level floor and above
the lower level ceiling.

I want as little current drop as possible. The generator provides
100 amps.

One of the contractors under consideration wants to use aluminum wire,
but I am more than willing to pay the premium between aluminum and
copper. I don't have an electrical "handibook" available.

What I am wondering:

1. Is 4/0 copper wire heavy enough?

2. Anyone know a supplier for about 70 feet of the stuff?

Our local electrical suppliers don't seem to want to provide a length
that short.

Thanks.

P.S. I'm really only interested in replies from those with an
educational or professional electrical background.

So is this for your grow op so the police don't see your utility bill?

In any case, for 1), current heats wire not voltage or wattage, so what
is the voltage as to calculate the current 17KW can generate? Amps
generate the heat. 220 or 115? With that size I will assume 220. 17K/220
= 77.3 amps. And I like being cautious, say AWG 3 for 220, 3/0 for 120.

http://en.wikipedia.org/wiki/American_wire_gauge

Probably industrial supply shops, as consumer hardware stores will not
carry this. As it gets worse. You need special tools to bend it, you may
need conduit and I strongly suspect local ordinance would require an
inspection or at least a licensed electrician.


Tonight I had to install a new shallow well system for a friend in
Essex. Pretty straight forward, pump, expansion tank, and new conduit
tube from the knife switch above on the floor joist, down to the cutoff
switch... to code.

We noticed the breaker supplied an outside light and an outlet too, so
we had to put in an new breaker and 12 ga, Romex to supply the pump on a
separate line, also required by code.

Electrical and plumbing is not really all that hard, about 20 years ago
I with some help changed my home over from knob and tube to modern day
romex, gpf switches, etc.., three years ago I redid the plumbing in
our place, including a new section of baseboard heating in one room. For
the water side of the system I used Pex pipe and Sharkbite fittings up
to the floors under the appliance or sink, and went with hard copper
from the floor up... I actually enjoy doing that stuff, But I guess my
bud could have waited for someone with "educational or professional
electrical background" and spent $700 for a $300 (parts) job we could
easily do ourselves. snerk.



I'll do light electrical work, such as replacing a wall switch or
ceiling fixture, but that's about it. The labor for the new generator
involves electricians and a plumber, and the charges for both services
are estimated at around $2500. The job has to be permitted, at least as
far as the plumbing goes. The genny is an LP gas appliance. I don't mess
with installing gas appliances or heavier duty electric, especially when
the wiring or pipes are to be concealed.


Coward.


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is Off
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Way OT, but needing some electrical advice Tim General 12 January 6th 10 01:03 AM
electrical generator - out of an electrical trolling motor??? Mic Electronics 12 May 10th 05 05:52 PM
Need help with electrical Derek General 2 June 21st 04 12:27 PM
Prop Size - Advice on Advice? Lloyd Sumpter General 8 December 31st 03 03:17 AM


All times are GMT +1. The time now is 01:38 AM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
Copyright ©2004-2025 BoatBanter.com.
The comments are property of their posters.
 

About Us

"It's about Boats"

 

Copyright © 2017