Any generator experts out there?
Greetings,
I have a Westerbeke 4.0KW gas genny in my boat, and I'm experiencing the following: The genny runs like a sewing machine, and when first started, the voltage settles right at 115. When a load is presented (A/C for example), I'll get the typical drop from the load while the genny adjusts, and then the genny will settle back to around 115. All is well at this point. The problem is, when the load is removed (when the A/C cycles), the voltage rises to 150 and stays there. I notice an increase in engine speed as well. My initial thought is that the voltage regulator might have gone south, but I don't know if this would explain the rise in engine speed. I guess if the regulator doesn't control the voltage, the engine speed will rise accordingly to satisfy the higher voltage, but I'm no electrical engineer, so it's just a guess. Any input would be greatly appreciated! I'm planning an anchor-out this weekend, and with the rains and heat/humidity in FL, I can't be without A/C!!! |
Any generator experts out there?
On Thu, 13 Jul 2006 14:38:35 -0400, wrote:
On Thu, 13 Jul 2006 13:30:51 GMT, wrote: Greetings, I have a Westerbeke 4.0KW gas genny in my boat, and I'm experiencing the following: The genny runs like a sewing machine, and when first started, the voltage settles right at 115. When a load is presented (A/C for example), I'll get the typical drop from the load while the genny adjusts, and then the genny will settle back to around 115. All is well at this point. The problem is, when the load is removed (when the A/C cycles), the voltage rises to 150 and stays there. I notice an increase in engine speed as well. My initial thought is that the voltage regulator might have gone south, but I don't know if this would explain the rise in engine speed. I guess if the regulator doesn't control the voltage, the engine speed will rise accordingly to satisfy the higher voltage, but I'm no electrical engineer, so it's just a guess. Any input would be greatly appreciated! I'm planning an anchor-out this weekend, and with the rains and heat/humidity in FL, I can't be without A/C!!! This is an alternator so engine speed only affects frequency. The regulator may in fact be bad but if it really increases engine speed there is another problem. I would suggect getting it looked at by someone with the tools to see what is really going on. You don't get the power for free, so under load the gas engine driving that alternator/generator must increase its throttle setting to keep up with the increased demand. When the demand goes away, the throttle evidently isn't closing back down, and the engine speed increases without that extra load on it. If poorly regulated, that can increase the voltage output as well. Think of your car idling with the lights on, the rev it up... the lights get brighter. Conversely, keeping the same engine speed turn the headlights off, and the voltage will rise. Does the engine speed ever slow back down on its own? Could it be as simple as a broken/missing throttle return spring? Or maybe a binding throttle linkage. |
Any generator experts out there?
|
Any generator experts out there?
|
Any generator experts out there?
Many thanks for everyone's input! I spend a couple of hours troubleshooting the genny on Saturday morning, and found the culprit. The governor was working properly, but wasn't returning the throttle to the idle position after the load was removed. Adjusted the linkage from the governor to the throttle body did the trick, in association with adjusting the governor to attain the proper voltage. I now need to throw a hertz meter on it to finalize the adjustement, but it now purrs at 120V, settles in at 120V under load, and returns to 120V when the load is removed. Now if I can figure out how to keep my A/C from cycling so much, I'll be in good shape!! |
Any generator experts out there?
|
Any generator experts out there?
|
Any generator experts out there?
If you could find a thermostat with different on and off temps that
might help. Then you set it to come on at 72 but not go off until 68. I know that heater thromostats have anticipator circuits to compensate for cycling but I don't think ac ones do. wrote: On Mon, 17 Jul 2006 12:39:10 -0400, wrote: Now if I can figure out how to keep my A/C from cycling so much, I'll be in good shape!! Is the unit oversized? That is the first suspect in short cycling. If it is sized right you can try more insulation, location of the thermostat or better air flow. Is it creating one small cool spot near the thermostat. That will cause short cycling. As the air spreads out it calls for cooling again. A fan might help. If the whole area is heating up quickly you need to reduce the heat load (insulation, window covering etc). That will also save money. I assume this is a boat so it is probably going to be hard to It's a 12,000 BTU unit on a 30' Sea Ray, so I think it's sized properly. It's the same BTU as the old unit, but the old unit seemed to bring the temperature of the boat down faster. During the day, it runs almost constantly, so under high heat load, it works overtime bringing the cabin temperature down. The heat load is pretty horrendous on these boats, especially here in Florida. I went from the tried and true copper tube thermostat to a new digital thermostat when I installed the new A/C, and I think the old technology is more fitting for a boat, because I did not have cycling problems with the old A/C system. The problem is, the A/C will bring the cabin down to temperature, but the temperature rises so quickly after the A/C cycles off, that it cycles right back on again. I bought and installed the optional remote temperature sensor, which I mounted in the return air duct, and this helped a little bit, but did not cure the problem. My next experiment will be to see if I can set the system so the fan runs continuously, and does not cycle off with the compressor. I'm thinking this may keep the air "mixed" better. I have two small fans in the cabin, but they sound like a P-51 Mustang at takeoff, so they're not something you can run at night! |
Any generator experts out there?
On 18 Jul 2006 10:49:31 -0700, "jamesgangnc"
wrote: If you could find a thermostat with different on and off temps that might help. Then you set it to come on at 72 but not go off until 68. I know that heater thromostats have anticipator circuits to compensate for cycling but I don't think ac ones do. This actually may be a function within the digital control, setting the temp differential......I need to dig into the manual for the controller..... |